Low voltage dynamic reactive power regulator (FTTK)
Low voltage dynamic reactive power regulator (FTTK)
Views:
Category:
Download:
Product Introduction
Parameters
◇Ambient temperature: -25°C to +55°C
◇Altitude: no more than 2000M
◇Atmospheric conditions: air humidity not exceeding 90%
◇Environmental conditions: media free of conductive dust
How to use
◇Main circuit: R, S, T: power supply connection terminal; U, V, W: connection to capacitor terminal
◇Control circuit: K+ terminal: positive side of the control voltage, K- terminal: negative side of the control voltage
◇Working power supply: L terminal: phase line (any one phase), N terminal: zero terminal, AC 220V access required on L, N line.
Security .
◇ The installation, maintenance and operation of this dynamic reactive power regulator is to be carried out by personnel with the relevant professional knowledge and skills.
◇ Determine if the power supply system is the same as the product ordered.
◇ Do not open the housing of the dynamic reactive power regulator at will to prevent electric shock.
Principle of operation .
FTTK series low-voltage dynamic reactive power regulator is a kind of "over-zero trigger" thyristor switch, the main circuit of the regulator adopts anti-parallel thyristor module, the control circuit board is composed of trigger, photoelectric isolation and logic control, the regulator combines heat sink, fan, temperature control, etc., with temperature control to start the fan, over-temperature protection function. FTTK adopts the principle of "over-zero trigger", no inrush current when putting in capacitors, dynamic response time≦20ms, it is a kind of power electronic switch for capacitor throwing.
Model naming rules:
Performance parameters:
Rated voltage | 380av±10%,480vac±10%,525vac±10%,690vac±10%。 |
Operating voltage | 100V - 260V AC |
Rated frequency | 50Hz-60Hz |
Rated current | 45A,55A,85A,95A,125A,165A |
Control voltage | DC12C/10mA control voltage supplied by the controller itself |
Dynamic response | ≦20ms |
Repeat cut | ≦40ms |
Pneumatic fan temperature | 55±3° |
Protection temperature | 85±3° |
Capacitor configuration table:
Serial number |
Model |
Capacitor capacity |
Common complementary Δ external |
FTTK-45G |
≦16Kvar |
FTTK-55G |
18-30Kvar |
|
FTTK-85G |
31-50Kvar |
|
FTTK-95G |
51-62.5Kvar |
|
FTTK-125G |
65-75Kvar |
|
FTTK-165G |
76-100Kvar |
|
Split Y connection |
FTTK-45G |
≦3*5Kvar |
FTTK-55G |
3*(5.5-10)Kvar |
|
FTTK-85G |
3*(11-17)Kvar |
|
FTTK-95G |
3*(18-20)Kvar |
Shapes and dimensions:
Model |
Mounting dimensions (mm) |
Opening size (mm) |
FTTK-45G/F |
203±8*37 |
176*116 |
FTTK-55G/F |
||
FTTK-85G/F |
||
FTTK-95G/F |
||
FTTK-125G/F |
176*152 |
|
FTTK-165G/F |
Reference technical parameters |
176-237 |
Wiring diagram:
6.1FTTK-45/55/85/95
Dimensions of the layout for mounting the regulator:
6.2FTTK-125G
6.3FTTK-165G
-